2 Killick Street
41,791 sq ft
Notting-Hill-Housing-Trust-Office-Space-2-Killick-Street-Office-Fit-Out-Project-Exterior
Notting-Hill-Housing-Trust-Offices-2-Killick-Street-Workplace-Design-Office-Fit-Out
Notting-Hill-Housing-Trust-Office-Space-2-Killick-Street-Office-Fit-Out-Project

2 Killick Street

Overview
2 Killick Street is located in Central London, just north of Euston Road in the borough of Camden. The main property entrance is situated on Killick Street, with a second entrance for cars via Collier Street. The property was constructed in 1991. The property has been designed exclusively for office use.

Maris Expertise
Maris Interiors have undertaken a full office design and fit-out project for Notting Hill Housing Trust consisting of 43,000 sq ft. We provided full refurbishment of the building including the complete replacement of air-conditioning systems, entrance areas and external works. Specifically, Notting Hill wanted to ensure that the space gave their staff excellent facilities including cafe, break out and collaboration areas.

We worked alongside Notting Hill and their consultants, Cushman Wakefield, for a number of months to ensure the scope of works and budgets were tailored to the specific requirements of the scheme.

Structure
Substructure
Piled foundations

Superstructure
Steel frame on a 9m x 9m grid, concrete floor slabs

Floor Loading
Offices 3.5KN/m2 (+1KN for partitioning)
Basement and plant enclosures 7.5KN/m2

Façade
Brick and concrete

Roof
Slate tiled pitched roof

Accommodation
Dimensions

Raised floor zone
150mm

Slab to slab height
Varies between 3.4m and 4.1m

Noise Rating
Offices (Open Plan) NR38
Reception NR40
WC areas NR40

Entrance Hall
Timber panelled walls

Refuse
Refuse and recycling bay within the rear of the building

WC / Bathroom Facilities
Male – 2no. urinals, 2no. WCs, 3no. wash-hand basins per floor
Female – 3no. WCs, 3no. wash-hand basins
Disabled WC – 1no. WC, 1no. wash-hand basin

Showers
Unisex shower located on the basement level

Cleaner’s Facilities
No designated facilities currently exist

Cycle
Provisions A single rack is located in the rear courtyard

Raised Floors
600 x 600mm, wrapped galvanised steel on adjustable pedestals

Ceilings
Fully demountable band raster suspended ceiling with metal tiles

Walls
Dry-lined with a painted finish

Doors, Frames & Skirting
Skirting – 100mm timber veneered
Doors – solid core veneer with painted frames
Riser doors – painted doors with painted frames

Building Services
Mechanical Services Design Criteria Air-conditioning load allowance
Lighting 15 w/m2
Power 25 w/m2
Occupants 10 w/m2

Mechanical Services
4 pipe fan-coil system

Mechanical Services Layouts
Yes, hand marked

Ventilation
14 litres per second per person (1no. person per 10m2)

Electrical Services
2no. EDF incoming 600A TPN services, terminating in isolators in the basement with a 350A rated copper rising bus bar system providing electrical sub main distribution to each floor via 100 A TP rated fused tap off units

Generator
2no. 500 kVA generators within the courtyard providing back up supply to the two EDF supply authority 600A services to the building

Lighting
Recessed twin lamp 1200mm x 300mm luminaires with Cat 2 louvres

Controls
Multi gang grids at central locations

Lighting Services
Layout Yes, hand marked

Fire Alarm System
Yes

Sprinkler System
No

Data
Existing throughout the building

Lifts
2no. 1000kg or 3no. person capacity

Security
CCTV and access control existing

Design Criteria
General occupancy
1 person per 10m2
Lifts – 1 person per 12m2
WC / bathrooms – 1 person per 10m2
Ventilation Limiting Factor 687 persons
WC / Bathroom Limiting Factor 750 persons
Emergency Escape Door / Staircase Widths 660 persons

Sustainability
BREEAM Rating N / A

Address


Size
41,791 sq ft
Landlord
HOW Engineering Services
Year
1991